41 (1) Every “A” Class division shall be constructed of steel or similar material, in either case stiffened so as to be capable of preventing the passage of smoke and flame th
roughout a standard fire test of 60 minutes duration; the division shall have an adequate insulating value having regard to the nature of the spaces adjacent thereto, and if the division is between spaces either of which contains adjacent combustible material, it shall be so insulated that, if either face of the division is exposed to a standard fire test of 60 minutes duration, the average temperature on the unexposed face of the division will not increase at any
...[+++]time during the test by more than 139°C above the initial temperature on that face nor shall the temperature at any one point thereon increase by more than 180°C above the initial temperature.41 (1) Toute cloison type A sera construite en acier ou autre matériau semblable, armaturée dans un cas comme dans l’autre de façon à pouvoir empêcher le passage de la fumée et des flammes pendant toute la durée d’un essai au feu standard de 60 minutes. Elle présentera un degré d’isolemen
t suffisant, compte tenu de la nature des locaux contigus, et, si elle sépare des locaux dont l’un ou l’autre comporte des matériaux combustibles en contact avec elle, elle sera isolée de telle sorte que, si l’une ou l’autre de ses surfaces est soumise pendant 60 minutes à un essai au feu standard, la température moyenne de la surface non exposée n’augme
...[+++]nte à aucun moment au cours de l’essai de plus de 139 °C au-dessus de la température initiale et que la température en un point quelconque ne s’élève pas de plus de 180 °C au-dessus de la température initiale.